Model A5LCY30/40/50/60FR Discharge Pipe Sensor
Resistance R25=230.0k + 1.0% - 1.0%
T°C
Resistance
(k)
T°C
Resistance
(k)
T°C
Resistance
(k)
T°C
Resistance
(k)
-6 1120.0 42 109.0 90 18.1 140 4.1
-4 1002.5 44 100.2 92 16.9 142 3.9
-2 898.6 46 92.2 94 15.8 144 3.7
0 806.5 48 84.9 96 14.8 146 3.5
2 724.8 50 78.3 98 13.9 148 3.3
4 652.2 52 72.2 100 13.1 150 3.2
6 587.6 54 66.7 102 12.3 152 3.0
8 530.1 56 61.6 104 11.5 154 2.9
10 478.8 58 57.0 106 10.8 156 2.7
12 432.9 60 52.8 108 10.2 158 2.6
14 392.0 62 48.9 110 9.6 160 2.5
16 355.3 64 45.3 112 9.0 162 2.3
18 322.4 66 42.0 114 8.5 164 2.2
20 292.9 68 39.0 116 8.0 166 2.1
22 266.3 70 36.3 120 7.1 168 2.0
24 242.5 72 33.7 122 6.7 170 1.9
26 221.0 74 31.4 124 6.4 172 1.9
28 201.6 76 29.2 126 6.0 174 1.8
30 184.1 78 27.2 128 5.7 176 1.7
32 168.3 80 25.4 130 5.4 178 1.6
34 154.0 82 23.7 132 5.4 180 1.5
36 141.0 84 22.1 134 4.8
38 129.3 86 20.7 136 4.6
40 118.7 88 19.3 138 4.3
Model A5MSY20/25/30BR
Resistance R25=20.0k + 1.0% - 1.0%
T°C Resistance (k) T°C Resistance (k)
-20 211.0 20 25.0
-15 150.0 25 20.0
-10 116.5 30 16.0
-5 88.0 35 13.0
0 67.2 40 10.6
5 51.9 45 8.7
10 40.0 50 7.2
15 31.8